    Red Team 1949  (formerly CHT Attack and Defense Team) In this rapidly changing Internet era, we maintain our original intention and create the best community to jointly exchange network technologies. You can obtain hacker attack and defense skills and knowledge in the forum, or you can join our Telegram communication group to discuss and communicate in real time. All kinds of advertisements are prohibited in the forum. Please register as a registered user to check our usage and privacy policy. Thank you for your cooperation.

    TheHackerWorld Official

Recommended Posts

有一台HP BL460C G7刀片服务器,运行有Vmware ESXi5.0操作系统,Vmware vCenter显示该把刀片服务器处于离线状态,但是可以ping通该刀片上的ESXi5.0的IP地址,连接到刀箱的管理口,未发现任何告警,使用该刀片的remote console,可以看到Vmware ESXi5.0的界面,按F2出现登录框,输入用户名和密码后,按回车没有反应,到机房接上显示器和键盘后,按回车仍然没有反应,但是一直可以ping通IP地址。

重启该把刀片后,在自检时按任意键查看详细自检信息,自检到阵列卡时,出现:
Slot 0 HP Smart ArrayP410i Controller
1783-Slot 0 Drive Array Contorller Failre!
[Command failure (cmd=0h,  err=00h,  dlu=013:4h)]

是阵列卡的报错,报错代码为1783,这种情况不能进入阵列卡BIOS查看阵列的配置情况、硬盘情况,需要更换阵列卡,由于该阵列卡集成在主板上,需要更换主板。

更换主板后,由于raid信息都在硬盘中,所以数据都能够识别,比能够进入操作系统。